Never miss your SPCC plan's five-year review
The owner or operator of a facility covered by EPA's oil pollution prevention rule must review and evaluate its SPCC Plan at least once every five years and document the review with a signed statement saying whether the Plan will be amended (40 CFR 112.5(b)). Any amendment the review calls for is due within six months.
EPA's oil pollution prevention rules (40 CFR part 112) apply to owners and operators of non-transportation-related onshore and offshore facilities that store, process, use or otherwise handle oil and could reasonably be expected to discharge oil in harmful quantities into navigable waters or adjoining shorelines (40 CFR 112.1(b)). A facility is exempt if its completely buried oil storage capacity is 42,000 U.S. gallons or less and its aggregate aboveground oil storage capacity is 1,320 U.S. gallons or less, counting only containers of 55 U.S. gallons or more (40 CFR 112.1(d)(2)).
The owner or operator of a covered facility must prepare in writing and implement a Spill Prevention, Control, and Countermeasure (SPCC) Plan (40 CFR 112.3). Except as provided for qualified facilities in 40 CFR 112.6, a licensed Professional Engineer must review and certify the Plan for it to be effective (40 CFR 112.3(d)).
The owner or operator must complete a review and evaluation of the SPCC Plan at least once every five years. If the review finds field-proven prevention and control technology that would significantly reduce the likelihood of a discharge, the Plan must be amended within six months of the review, and the amendment implemented as soon as possible, but not later than six months after it is prepared. The review must be documented with a signed statement saying whether the Plan will be amended (40 CFR 112.5(b)).
At a glance
| Rule | 40 CFR 112.5(b), EPA oil pollution prevention |
|---|---|
| Review | At least once every five years |
| Amendment after review | Within six months, if the review calls for new technology |
| Implementation | As soon as possible, within six months of preparing the amendment |
| Record | Signed statement at the start or end of the Plan, or in a log or appendix |
| Technical amendments | Certified by a Professional Engineer, except as provided in 112.6 |
The five years run from the date the facility became subject to part 112; for facilities in operation on or before August 16, 2002, from the date the last review was required (40 CFR 112.5(b)).
Who is responsible?
The owner or operator of the facility. It must keep a complete copy of the Plan at the facility if the facility is normally attended at least four hours a day, otherwise at the nearest field office, and make it available to the EPA Regional Administrator for on-site review during normal working hours (40 CFR 112.3(e)).
Changes at the facility need an amendment too
Apart from the five-year review, the Plan must be amended when a change in facility design, construction, operation or maintenance materially affects its potential for a discharge, such as commissioning or replacing containers, changing piping or secondary containment, or changing the product stored. The amendment must be prepared within six months and implemented within six months after it is prepared (40 CFR 112.5(a)).
Tracking it with ExpirySuite
- Add each facility's SPCC Plan and record the date its next five-year review is due.
- Reminders arrive 60, 30, 14, 7 and 1 day before the due date and on the due date itself.
- Assign a responsible person (for example your environmental or facility manager) so the right person gets the reminder.
- If a date passes, managers get overdue reminders 3, 7 and 14 days later.
- Ask your consultant or Professional Engineer to upload the signed review statement or amended Plan through a secure upload link, valid for 14 days; no account is needed.
Frequently asked questions
- How often must an SPCC Plan be reviewed?
- At least once every five years (40 CFR 112.5(b)).
- How do I document the review?
- Sign a statement saying whether you will amend the Plan, at the beginning or end of the Plan or in a log or appendix. The rule gives this wording: "I have completed review and evaluation of the SPCC Plan for (name of facility) on (date), and will (will not) amend the Plan as a result." (40 CFR 112.5(b)).
- Does every amendment need a Professional Engineer?
- Technical amendments must be certified by a Professional Engineer, except as provided in 40 CFR 112.6 (40 CFR 112.5(c)).
- Is a small facility exempt?
- A facility is exempt if its completely buried storage capacity is 42,000 U.S. gallons or less and its aggregate aboveground storage capacity is 1,320 U.S. gallons or less, counting only containers of 55 U.S. gallons or more (40 CFR 112.1(d)(2)).
Sources
- eCFR: 40 CFR 112.5, Amendment of SPCC Plan by owners or operators
- eCFR: 40 CFR 112.3, Requirement to prepare and implement an SPCC Plan
- eCFR: 40 CFR 112.1, General applicability
Last checked: Sep 30, 2026 · This page summarises official sources for general information and is not legal advice. Check the linked sources for current rules and fees.
Made for SPCC plan five-year review (EPA) (US)
A ready template for SPCC plan five-year review (EPA) (US) with sensible validity defaults, so you enter less and track more.
Reminders on time
Email alerts at 60, 30, 14, 7 and 1 day before each SPCC plan five-year review (EPA) (US) expires, plus overdue escalation to managers.
Assign an owner
Give each SPCC plan five-year review (EPA) (US) an owner and let employees update their own via a secure link — no login needed.