Never let a building or site of your company end up with an expired gas seal
Indoor gas installations in use are inspected every two years by an SEC-authorised certification body; after two consecutive green seals, every four (DS 66, Article 33; SEC Res. 1.250/2009, Article 1-4). In condominiums the administrator requests it; a red or yellow seal means fixing the defects and re-inspecting.
Chile's Regulation on Indoor Gas Installations and Gas Meters (DS 66 of 2007) requires the owners of indoor gas installations to hire certification bodies authorised by the Superintendency of Electricity and Fuels (SEC) for the certification of the installation, whenever it is modified and for its periodic inspection, following the procedure set by the Superintendency (Article 33). Managers and management committees of co-owned buildings are responsible for keeping the common installations in good condition and must request their periodic inspection (Article 35). That procedure is SEC Exempt Resolution 1.250 of 2009: only authorised certification bodies may carry it out (Article 1-2), and it applies to all indoor gas installations except those used exclusively for production or manufacturing processes; for houses in use, periodic inspection is voluntary (Article 1-3).
Installations in use are inspected every two years, counted from the date of the Approval Certificate issued at certification or from the previous Periodic Inspection Certificate. If the installation obtains two consecutive green seals, subsequent inspections take place every four years, for as long as it keeps a green seal (Article 1-4, letter b). Modifications are certified once completed, and that certification is valid until the date of the periodic inspection set by the building's general seal (Article 1-4, letter c). For all purposes, valid seals are required, meaning seals that respect that frequency (Article 1-4).
The certification body rates each installation: a green seal if it has no defects (Article 5-3), a red seal if it has one or more critical defects (Article 5-4) and a yellow seal if it has major or minor but no critical defects (Article 5-5); collective buildings also receive a general seal (Articles 5-6 to 5-9). The body issues a Periodic Inspection Certificate showing the seal's number and colour (Article 3-8) and makes it available to users and the building manager within 5 working days of issue (Article 3-9). With a red or yellow seal, the defects must be fixed by an authorised gas installer and a new inspection carried out (Article 4-4).
At a glance
| Frequency | Every 2 years from the Approval Certificate or from the previous Periodic Inspection Certificate (Res. 1.250, Article 1-4, letter b) |
|---|---|
| After two consecutive green seals | Every 4 years, for as long as the installation keeps a green seal (Article 1-4, letter b) |
| Scope | All indoor gas installations except those used exclusively for production or manufacturing processes; voluntary for houses in use (Article 1-3) |
| Who inspects | Only certification bodies authorised by the SEC, through a gas inspector (Articles 1-2 and 2-9) |
| Seals | Green: no defects; yellow: major or minor defects; red: one or more critical defects (Articles 5-3 to 5-5) |
| Certificate | Periodic Inspection Certificate with the seal's number and colour, delivered within 5 working days (Articles 3-8 and 3-9) |
| No access | If access is refused or the premises are unoccupied, the installation is rated with a red seal (Article 4-6) |
The SEC sets the certification and inspection protocols by resolution (Res. 1.250, Article 1-2) and oversees compliance (Article 6-1). Modifications to an installation are certified once completed; the unmodified part follows the periodic inspection calendar (Article 1-4, letter c).
Who is responsible?
The owner of a building is responsible for keeping its indoor gas installation in good condition; in co-owned buildings, owners answer for the individual installations and managers for the common ones (Res. 1.250, Article 4-1; DS 66, Article 35). Owners and managers must hire a certification body at the time set by Article 1-4 (Article 4-2; DS 66, Article 33) and give access to the SEC, certification bodies and gas companies (Article 4-6; DS 66, Article 39). The manager must keep available the copy of the installation declaration and its documentation (DS 66, Article 36). If defects are found, owners, users and the manager must inform the SEC in writing of the solution they will adopt (DS 66, Article 38).
If the deadline passes
For all purposes, valid seals are required, meaning seals that respect the frequency in Article 1-4 (Res. 1.250). Any breach of DS 66 is punished by the Superintendency of Electricity and Fuels under Law 18.410 and the regulation on penalties for electricity and fuels (DS 66, Article 105). If the inspection finds critical defects, the certification body informs users within 24 hours (Article 3-14) and, for critical defects requiring immediate action, the gas company, which cuts off supply unless the conditions in Article 4-7 are met; supply is restored only once it is shown that the defect no longer exists (Article 4-8).
The building's general seal
In a collective residential, commercial, office, public-use or shopping-centre building, the certification body also rates the installations as a whole (Res. 1.250, Article 5-6). An installation in use receives a general green seal when its ancillary works and collective appliances have no defects, individual installations with a red seal do not exceed 10% of the seals issued and those with red and yellow seals do not exceed 25% (Article 5-7); it receives a red seal when the ancillary works or collective appliances have critical defects or the individual installations with a red seal exceed 25% (Article 5-8).
Tracking it with ExpirySuite
- Add each building, premises or plant as a site and record as the expiry the date two years after the Approval Certificate or the latest Periodic Inspection Certificate; if the installation already has two consecutive green seals, four years.
- Email reminders arrive 60, 30, 14, 7 and 1 day before expiry and on the expiry day.
- The building manager or the certification body can upload the new Periodic Inspection Certificate through a secure link that is valid for 14 days and needs no account.
- Assign a responsible person, such as the maintenance manager or the building manager; if the seal expires, managers get further reminders 3, 7 and 14 days later.
Frequently asked questions
- How often is the periodic gas inspection carried out?
- Every two years, counted from the Approval Certificate or from the previous Periodic Inspection Certificate; after two consecutive green seals, every four years for as long as the green seal is kept (SEC Exempt Resolution 1.250/2009, Article 1-4, letter b).
- Which installations are covered?
- All indoor gas installations, except those used exclusively for production or manufacturing processes. For houses in use, periodic inspection is voluntary (Article 1-3).
- What does each seal colour mean?
- Green: the installation has no defects (Article 5-3). Red: it has one or more critical defects (Article 5-4). Yellow: it has major or minor defects, but no critical ones (Article 5-5).
- What do I do if the installation gets a red or yellow seal?
- Fix the defects through an authorised gas installer and have a new inspection carried out (Article 4-4), and inform the SEC in writing of the solution to be adopted (DS 66, Article 38).
- Who requests the inspection in a co-owned building?
- Managers and management committees, as representatives of the community, must request the periodic inspection of the common installations (DS 66, Article 35); each owner answers for their individual installation (Res. 1.250, Article 4-1).
Sources
- Resolución Exenta 1.250 de 2009 (Superintendencia de Electricidad y Combustibles), procedimientos de certificación e inspección periódica de instalaciones interiores de gas: artículos 1-2, 1-3, 1-4, 3-8, 3-9, 3-14, 4-1 a 4-8, 5-3 a 5-9 y 6-1 (LeyChile, BCN)
- Decreto 66 de 2007, Reglamento de Instalaciones Interiores y Medidores de Gas: artículos 33, 35, 36, 38, 39 y 105 (LeyChile, BCN)
Last checked: Oct 7, 2026 · This page summarises official sources for general information and is not legal advice. Check the linked sources for current rules and fees.
Made for periodic indoor gas installation inspection (SEC seal) (Chile)
A ready template for periodic indoor gas installation inspection (SEC seal) (Chile) with sensible validity defaults, so you enter less and track more.
Reminders on time
Email alerts at 60, 30, 14, 7 and 1 day before each periodic indoor gas installation inspection (SEC seal) (Chile) expires, plus overdue escalation to managers.
Assign an owner
Give each periodic indoor gas installation inspection (SEC seal) (Chile) an owner and let employees update their own via a secure link — no login needed.